Original Source Document Full PDF Version
← Hager

Hager Wire Run Gauge Guide image on page 1

It is very important that the wire you choose is large enough to carry the amount of current from your power supply to your load and access control. A common mistake in sizing wire is to turn to the NEC wire size charts to determine how much amperage a wire can safely handle. This method of sizing wire will lead to a very inefficient system since these tables are generally based on higher voltage (110/220 volts A/C), and the main concern is safely transmitting the power without heat buildup. In a low voltage system, we are of course concerned with safety, power loss dictates wire size even more. A 20% loss of power in a 12 volt line is 2.4 volts. This would yield 9.6 volts at the load and may prevent some devices from operating.

The below chart shows the appropriate wire gauge for specific current draw, voltage, and wire length based on an industry standard 10% voltage drop. The wire voltage drop is not the only factor that should be considered with wire sizing though. The power supply output should also be considered. Unless otherwise indicated, the voltage supplied to the load should always be within an industry standard 10% of the desired load, meaning a 24 volt electric strike should have between 21.6 and 26.4 volts at the device (24v \pm 2.4v) . This means that if a 24 volt power supply puts out 5% lower voltage than it is rated, then a 5% maximum voltage drop wire run is recommended.

To use the chart below:

  • 1) Select the next higher current draw needed for your application.
  • 2) Follow the row to the right and select the desired voltage being used for your application.
  • 3) Continue to the right and select the shortest wire run that is still longer than the wire run being installed for your project.
  • 4) Follow the column up to see the recommended wire size to be used.

Example: You are installing a dual voltage electric strike rated fr 600/300mA @ 12/24VDC. Your 1.0A power supply is installed in an electrical closet approximately 200 feet down the hall. Your specification indicates the use of 24VDC throughout the system.

  • 1) The electric strike is rated for 300mA @ 24VDC, therefore, you would select 500mA from the table.
  • 2) The specified voltage is 24V. For 24V, the shortest wire run listed in the table longer than 200ft is 225ft.
  • 3) The column indicates that a minimum wire gauge of 20 Gauge should be used.

Total Voltage 12 14 16 18 20 22
Amps Gauge Gauge Gauge Gauge Gauge Gauge
0.25 A 12 V 1500 ft 1000 ft 600 ft 375 ft 225 ft 150 ft
24 V 3000 ft 2000 ft 1200 ft 750 ft 450 ft 300 ft
0.5 A 12 V 750 ft 500 ft 300 ft 190 ft 110 ft 75 ft
24 V 1500 ft 1000 ft 600 ft 375 ft 225 ft 150 ft
0.75 A 12 V 500 ft 300 ft 185 ft 125 ft 75 ft 50 ft
24 V 1000 ft 600 ft 375 ft 250 ft 150 ft 100 ft
1.0 A 12 V 400 ft 250 ft 150 ft 100 ft 50 ft 35 ft
24 V 800 ft 500 ft 300 ft 200 ft 100 ft 75 ft
1.25 A 12 V 300 ft 190 ft 120 ft 75 ft 45 ft 30 ft
24 V 600 ft 380 ft 240 ft 150 ft 90 ft 60 ft
1.5 A 12 V 250 ft 150 ft 100 ft 65 ft 40 ft 25 ft
24 V 500 ft 300 ft 200 ft 125 ft 80 ft 50 ft
1.75 A 12 V 230 ft 135 ft 85 ft 50 ft 35 ft 20 ft
24 V 460 ft 275 ft 170 ft 100 ft 70 ft 40 ft
2.0 A 12 V 200 ft 120 ft 75 ft 45 ft 30 ft 15 ft
24 V 400 ft 240 ft 150 ft 90 ft 60 ft 35 ft
2.25 A 12 V
24 V
175 ft
350 ft
200 ft
400 ft
65 ft
130 ft
40 ft
80 ft
25 ft
50 ft
2.5 A 12 V
24 V
150 ft
300 ft
95 ft
190 ft
60 ft
120 ft
35 ft
75 ft
2.75 A 12 V
24 V
140 ft
280 ft
85 ft
170 ft
50 ft
100 ft
3.0 A 12 V
24 V
130 ft
260 ft
80 ft
160 ft
50 ft
100 ft

Rev -, Rev Date: 12/3/2014 Page 1 of 1