2-5/16 Typ
(58.7
13/16 Typ
(20.6)
For
Fire Rated Mullion
Installations Only #10-24 Tap (Std.) or SNB (4 Places)
See Notes 9 & 14
Notes:
- 1. Do not scale drawing
- 2. Dimensions are in inches (mm).
- 3. LHR door shown. Preparation is typical for both door hands.
- 4. Minimum door stile width: 4-1/2(114).
- 5. Prepare mounting holes when installing the device.
- 6. Unreinforced frames require blind rivet nuts (by others) to mount the strike.
- 7. Dimension from door face.
- 8. For recommended door reinforcements see template T30800. Unreinforced doors require SNB option to mount the device components and strike interlock.
- 9. Holes for optional SNB: 9/32 (7.00) dia. inside door face; 3/8 (9.50) dia. outside door face.
- 10. Provide door stiffeners as needed to prevent door collapse due to installation with power tools, door use, or abuse.
- 11. Device mount to hinge stile (not shown) requires hole location and preparation during device installation.
- 12. For outside trim preparation see appropriate trim template.
- 13. For electrical devices (suffixes M91, M92, M93, M94, M97) also see template T30890
- 14. These hole(s) MUST be field located using physical part as template, after installation is complete and device is fully operational.
Strike Preparation Detail
| FRAME | MULLION | ||
| TEMPLATE | SERIES | SIZE | ILLUSTRATION |
| T30882 | 700 Series |
1-1/2" x 3"
(38 x 76) |
Doors 1-1/2" Mullion Width |
| T31074 | 900 Series |
2" x 3"
(51 x 76) |
Doors 2" Mullion Width |
| T31075 |
FE700 Series
WS700 Series |
||
| 1 | |||
CAUTION: Width of mullion used with exit device will affect device backset. Determine Mullion Series and Width before prepping doors for exit devices.
ED5200SA Series SecureBolt® Fire Exit Devices with 730F77 Strike
3-5/8
(92)
3-5/8
(92)
39-15/16
(1014)
Finished Floor
(31.8)
<u>1-1/4</u>
(31.8)
1/4-20 Tap (Std.)
See Note 9 (SNB) -4 Places-
Application for Fire Labeled Metal Door and Frame or Mullion
DO NOT SCALE DRAWING T30924
TEMPLATE NUMBER
T30924-3 11-18
(3)