Trouble-Shooting Your New Door Holder
Open the original PDF document
View PDFTroubleshooting Your New Door Holder
SARGENT
ASSA ABLOY
For installation assistance, contact SARGENT at 800-727-5477 • www.sargentlock.com
PROBLEM
Does not hold
POSSIBLE CAUSE
Power not turned on.
- Ground wire not connected to "COM" on terminal strip.
- Power wire not connected to correct power slot on terminal strip.
For single voltage coils – one wire attaches to ground, the other is attached to the power wire.
• Contact plate is not sitting completely flat across circular ring of the coil.
• Check line voltage coming from power supply (range +/-10%).
- For DC coils reverse polarity. Switch position of wires on terminal strip.
- Dirt or cleaning solvent on contact plate or on circular ring of coil; wipe with very fine emery cloth.
- Power wire not connected to correct power slot on terminal strip.
- 12VAC input instead of 12VDC
• Contact plate not sitting completely flat across the circular ring of the coil.
REV-2