Trine EN400 & EN400RP Electric Strike Installation Instructions

Open the original PDF document

View PDF

TROUBLESHOOTING

Possible Trouble Probable Cause Suggested Remedy
Door lockset is not
secured by Electric
Strike
1) Centerline of lockset is not
properly aligned to the
centerline of the electric strike.
Check for proper cutout installation of Electric Strike by
referring to template and door frame and lockset position.
2) Latch does not project Check for excessive gap between door and jamb.
properly into the cavity of the
electric strike
Check that lockset is compatible with EN series cavity and requirements. If necessary, use other type of lockset
or Electric Strike (refer to Trine Catalog for more information).
3) Latch Spring broken
or missing
Hold Electric Strike so that wiring faces down and apply pressure to Latch. Verify that Latch releases and that
there is sufficient Spring tension to push it to closed positionwhen released. If Latch does not have Spring
tension, disassemble Electric Strike and inspect for improperly installed or broken Spring.
Electric Strike
does no energize
1) Wiring to electric strike is
open or shorted.
Check that electrical connections are secure and that no fraying has occurred during installation. Use voltmeter
to verify that Electric Strike is receiving energizing voltage and that wiring is not shorted.
(activate) 2) Insufficient voltage to
electric strike.
Verify that voltage rating on Electric Strike label is compatiblewith voltage from secondary transformer
(12V or 24V). If voltages do not match, either replace transformer or change Electric Strike or Coil Assembly.
Use voltmeter to verify that Electric Strike is receiving proper voltage and that wiring is not shorted.
If voltage is too low because wire size is too small for length or wiring to Electric Strike (see
wiring-length data on previous page), either replace wiring or use transformer with higher VA rating.
3) Slider does not move when
coil receives proper voltage
Using an OHM meter, verify that resistance of the Coils matches the chart on page 3. If Coil is open (burned out),
verify that transformer for Electric Strike has correct voltage current AC/DC and is wired correctly. AC Coils do
not operate at continuous duty, or on DC voltage.
Check that Slider (2) floats freely, as follows:
Remove Electric Strike from jamb and hold with wires facing up. Test that Strike is locked by applying pressure
to Latch. Then turn Strike upside down with wires facing down and verify that Latch opens freely by applying
pressure. The locking Slider (#2) must float freely for unit to operate properly.
Electric Strike energizes
but does not disengage
1) Lockset is applying pressure
to electric strike, preventing
latch from releasing.
Check for proper cutout installation of Electric Strike. Latch requires proper clearance to open correctly and
provide path for Lockset Latch to engage Strike.
the lockset Check that Lockset Latch is not binding to bottom of Strike cavity due to door sag.
Check if foam insulation or the materials around door jamb are preventing door from closing flush, causing
door to put pressure on Latch.

FOR ADDITIONAL INFORMATION, HELP, ACCESS TO SPECS ON A OUR FULL LINE OF PRODUCTS, OR ADDITIONAL CONTACT OPTIONS PLEASE VISIT OUR WEBSITE www.trineonline.com

V. 18.0111

TRINE ACCESS TECHNOLOGY

PHONE: (203) 730-1756 FAX: (203) 730-1781 2 PARKLAWN DRIVE, BETHEL, CT 06801 email: customerservice@trineonline.com website: www.trineonline.com

EN400 & EN400RP ELECTRIC STRIKE

INSTALLATION INSTRUCTIONS

Congratulations on the purchase of this quality TRINE security product. This product has been designed to install easily, perform reliably, and provide years of trouble free security.

BEFORE proceeding with your installation, please review the following list of features. If you have any questions after reading this document please call TRINE's TECHNICAL SUPPORT (203) 730-1756 EXT. 447, or visit the TRINE web site at www.trineonline.com

PARTS LIST

Index No. Name Part Number
1 EN400 Latch EN-LCH
2 EN400RP Latch EN- RPLCH
3 Slider EN-SLR
4 Coil Assembly (12V) EN-CA-12DC or EN-CA-12AC
Coil Assembly (24V) EN-CA-24DC or EN-CA-24AC
5 Screws (2) #4-40 x 1/8" (Cover) EN-SCR 1/8
6 Frame Cover EN-FR.C
7 Screws #4-40 x 1/4" (Coil) EN-SCR 1/4
8 Frame ** EN-FR400
9 Assembly Pin* EN-ASS.PN
10 Spring EN-SPR
11 Latch Pivot Pin EN-LCH-PV-ST
12 Slider Guard EN-GRD
13 Mounting Screws (2) #12-24 x 1/2" EN-MTS
14 Shim Kit (3) 1/16" Shim EN-UNV-SHIM
15 Shim Screws (2) #6-32 x 1/4" EN-SHIM-SCR-S
16 Shim Screws (2) #6-32 x 3/8" EN-SHIM-SCR-L

24DC 0.15 164.0 Intm./Cont. Silent

UL LISTED - 10B fire rated (class A, 3-hour, Single Swing Doors) -- [Except EN400RP configuration]

UL LISTED - 294 Access Control System Units

UL LISTED - 1034 Burglary Resistant Locking Mechanism for Indoor or Outdoor Use

ANSI/BHMA - A156.5 - 1992 - 4-7/8" x 1-1/4" Fits Cutout Specification A115.1 (with Slight Jamb Modification)

BHMA - Grade 1

NYC MEA - 79-01-E

NOTE: UL fire listing is void when using fail safe action or RP latch (400RP) for Rim Panic Devices.

All models have bene evaluated for the following performance levels per UL 294 6th edition:

Destructive
Attack
Access Control
Line Security
Endurance Standby Power
I I IV I

Listed Class 2 Power-limited burglary power supply

1

.1

.4

RIGHT HAND REVERSE (ORDER LH) LEFT HAND REVERSE (ORDER RH)

HANDING OF DOOR IS ALWAYS DETERMINED FROM THE OUTSIDE

HANDING DETERMINATION

Door handing is determined by the position of the hinges, as viewed from the outside of the room or building. If the door hinges are on the left, the door is termed left handed: if the door hinges are on the right, the door is termed right handed. Also a door is either inswinging (opens into the room), or outswinging (opens to the outside of the room).

400 LATCH FOR CYLINDRICAL & MORTISE LOCKS LATCH ASSEMBLY Prepare the Latch for

assembly. Position the

Spring as shown and

pass the assembly pin

through the two parts.

Latch and Latch

Insert the Slider as

Fail-Secure or

Fail-Safe position

as shown.

RP LATCH (A) FOR RIM PANIC SWAP LATCHES DEVICES

At 5 (Below) you may switch out the standard Cylindrical/Mortise Latch for the RP (rim panic) Latch.

Note: RP Latch is NOT Fire Rated (it is Outdoor rated)

RIGHT HAND ASSEMBLY

Fail-Safe

Assembly

Pin

(2)

Disassemble the Back Cover and the solenoid of the Left Hand configured EN strike.

Using the Assembly Pin, push the Latch Pivot Pin out.

Take the Latch & Spring and the Slider Guard out of the frame.

LEFT HAND ASSEMBLY

Disassemble the Back Cover and the solenoid of the Right Hand configured EN strike.

Using the Assembly Pin, push the

Take the Latch & Spring and the Slider

Dimple shows Slider position

Align the Slider with the pick guard ribs as shown.

Assemble the Slider Guard over the Slider.

Assemble the Slider Guard over the Slider.

Insert the Latch Pivot Pin making sure that the flared pin head is towards the right as shown.

Pass the Latch Pivot Pin through the Frame, Latch and Spring.

(The assembly pin will fall off the opposite end. Save this pin for future use.)

Finish the assembly by installing the Cover and securing it with the two assembly Screws.

Assemble the Solenoid and secure it with the solenoid Screw as shown.

Insert the Latch Pivot Pin

Frame, Latch and Spring.

this pin for future use.)

making sure that the flared pin

head is towards the left as shown.

Pass the Latch Pivot Pin through the

Finish the assembly by installing the Cover and securing it with the two assembly Screws.

Latch Pivot Pin out.

Guard out of the frame.

Figure 4. Position of Electric Strike for Left Hand Inswinging and Right Hand Outswinging Door

as shown in figure (4).

NOTE

The EN Electric Strike must be installed with coil assembly up (wiring toward top of unit). In this position, the Electric Strike will be locked without power, Fail Secure, or locked with power, Fail Safe action. Before performing Handing Procedure, view Electric Strike in up position (wire leads at top) to determine if a handing change is required.

The position of the Electric Strike in the door

and a lefthanded door. For these installations,

In a similar manner, the position of the Electric

Electric Strike position in the door jamb will be

Strike in the door jamb will be the same for a

lefthanded reverse bevel door and a right

-handed door. For these installations, the

Figure 3.

Position of

Electric Strike

for Right Hand

Inswinging and Left Hand

Outswinging

Door

the Electric Strike position in the door jamb

will be as shown in Figure 3.

Cont... Page 2 Door Handing Determination INSTALLATION PROCEDURE:

  • For new or replacement installation in wood jamb will be the same for a right-handed door or metal jambs.
    • 1. Verify that voltage rating of Electric Strike is compatible with supply voltages of installtion. Coil voltages are color coded.

WIRE LEAD CODE/STRIPE
12AC Blue/Orange Stripe
12DC 2 Orange Stripe
24AC Blue/Black Stripe
24DC 2 Black Stripe

2. Using template supplied with Electric Strike. mark door jamb for cutout and screw holes.

For proper installation, center line of latches must be aligned with center line of Electric Strike.

  • 3. Prepare door frame (cut out jamb if required) for Electric Strike. Leave sufficient space for splicing between power supply wiring and Electric Strike wiring.
  • 4. If required, run new wiring to door frame mounting hole. See figure 10 for typical wiring installations. Refer to wiring chart below for correct wire size. (Total wiring length includes routing to door-release push button).

Total Wiring Length

To Transformer 12V 24V
Up to 50 Ft 18AWG 20AWG
50 to 150 ft 16AWG 18AWG
150 to 300 ft 14AWG 16AWG
300 to 600 ft 12AWG 14AWG

For DC operation, to obtain an audible signal when Electric Strike is energized. install buzzer type BZ-12 for 12VDC operation, or BZ-24 for 24VDC operation (purchased seperately), as illustrated in figure 10. 5. Hold Electric Strike upright (wiring toward top) and determine if handing is required. If so, perform handing procedure.

  • 6. Splice Electric Strike wiring to supply wiring. Secure with wire nuts (supplied).
  • 7. For wood and aluminum door jambs, drill pilot holes for securing Electric Strike to door jamb. For steel and aluminum door iambs, secure Electric Stike to existing mounting tabs.
  • 8. Install Electric Strike into door jamb and secure with flat head mounting screws (supplied).
  • 9. Verify that door operates correctly when Electric Strike is energized and not energized.

NOTE

  • 1. Rectifier can be located either between transformer and push button, or between push button and electric strike.
  • 2. Use either a silicon rectifier or a current regulating rectifier for converting the AC voltage at the transformer secondary to the DC for operating the electric strike.

SAMPLE WIRING DIAGRAMS FOR THE EN SERIES

Figure 10a. USING DC TRANSFORMER

Figure 10b. USING ACTRANSFORMER

* The rectifier can be positioned before of after the push button in the circuit. The LC module can ONLY be positioned after the push button as shown above.

*** When wiring the optional buzzer, polarity must be observed. Connect the (+ or RED) positive wire to the (+) positive side of the circuit and the (- or BLACK) negative side wire terminal to the negative side of the circuit

.3

circuit.