Edwards Signaling Light Output White Paper

Open the original PDF document

View PDF

A light output/light source discussion

Viewer Effective Light Output (VELO)

Effective signaling depends on both perception and understanding of the signal being transmitted. In the case of audible signals it is important to select a tone (e.g. bell, horn, siren) that not only conveys meaning but is also distinguishable from ambient (or background) sounds. Loudness is also an important factor – enough to be perceived over ambient dB but not too much that either distortion or listener damage occur.

These same type of factors affect visible signal selection. Ambient or background light may affect the choice of light source (e.g. steady, flashing, rotating, or strobe) while message type may dictate color choice (e.g. red for stop or danger).

Viewer perception (specifically the ability of the viewer to effectively see and comprehend the visual signal) is perhaps the most important feature of any visual signal.

Edwards' AdaptaBeacons have thus been designed to maximize viewer perceptibility. This focus on Viewer Effective Light Output (VELO) is most noticeable in the Edwards lens design. The unique double fresnel lens results in four illumination characteristics that significantly enhance viewer perception.

  • 1. The refractive feature of the inner fresnels causes the lens to fill; resulting in a rectangular column of light. This increases the "dwell" time of illumination thus significantly enhancing retinal retention.
  • 2. Light sources are positioned in the focal point of the lens thus enabling the lens-magnifying ring to effectively project the visual signal.
  • 3. The refractive external fresnels function also to diffuse the light. This enhances visibility for viewers located adjacent to the beacon.
  • 4. By ensuring that the lens is filled with light any "hot" spots are eliminated. This is particularly important to viewer perception when strobe light sources are involved. While hotspots generate high light output numbers, they generally result in decreased viewer perception (as viewers squint or turn away in order to avoid the flash). Additionally, the glare tends to wash out lens color resulting in a "white" flash – thus minimizing the color-coded message.

Light Output Data

All manufacturers light output information (Edwards included) needs to be evaluated against many criteria including: distance at which light is to be viewed, lens color, amount of lens pigmentation, viewer perceptibility, and in the case of strobes, VELO.

Currently there are no standardized agency testing criteria for measuring light output of general (non-fire alarm) visual signals. For this reason Edwards has opted to specify strobe tube output in joules, resultant effective candela, and peak candela ratings. See Table 1 for Edwards Strobe Light Output Data.

Strobe Tube Life Data

Strobe tube manufacturers all supply tube life data. Edwards has opted, when using this information, to report effective tube life to only a 25% decrease in light output. (Obviously the greater the decrease the longer will be the stated tube life). See Table 1 for Edwards Strobe Tube Life Data.

Table 1. Edwards Strobe Tube Light Output and Life

Cat. No. Strobe Tube
Cat. No.
Tube Life
(hrs)*
Joules Effective
Candela**
Peak
Candela
57EDF Series 92-ST 3,000 23 1265 2,300,000
89STR Series Not Replaceable 1,000 3 150 300,000
89SMSTR Series Not Replaceable 1,000 3 150 300,000
90 Series 92-LST 5,000 14 770 1,400,000
91B Series 91B-ST 3,000 3 165 300,000
92EX Series 92-LST 5,000 14 770 1,400,000
92EXB Series 92-LST 5,000 14 770 1,400,000
92EXC Series 92-LST 5,000 14 770 1,400,000
92-N5 Series 92-LST 5,000 14 770 1,400,000
92-R5 & -S1 Series 92-ST 3,000 8 440 800,000
92PLC Series 92-LST 5,000 14 770 1,400,000
92PLC-DF Series 92-ST 3,000 8 440 800,000
93 Series 92-ST 3,000 8 440 800,000
93DF Series 92-ST 3,000 11 605 1,100,000
94 Series 92-ST 3,000 8 440 800,000
94DF Series 92-ST 3,000 11 605 1,100,000
94DDV2 Series 92-ST 3,000 8 440 800,000
94DV2 Series 92-ST 3,000 8 440 800,000
95 Series 92-LST 5,000 14 770 1,400,000
96B Series 91B-ST 3,000 3 165 300,000
96DV2 Series 91B-ST 3,000 3 165 300,000
97 Series 92-ST 3,000 8 440 800,000
97DF Series 92-ST 3,000 8 440 800,000
97DEX Series 92-ST 3,000 8 440 800,000
97DEXB Series 92-ST 3,000 8 440 800,000
97DEXC Series 92-ST 3,000 8 440 800,000
97DEXC-GW 92-ST 3,000 8 440 800,000
97DEXBC-GW 92-ST 3,000 8 440 800,000
97DEXCC-GW 92-ST 3,000 8 440 800,000
97EX Series 92-ST 3,000 8 440 800,000
97EXB Series 92-ST 3,000 8 440 800,000
97EXC Series 92-ST 3,000 8 440 800,000
98B Series 91B-ST 3,000 3 165 300,000
99B Series 91B-ST 3,000 10 550 1,000,000
101 Series 91B-ST 3,000 3 165 300,000
102 Series Not Replaceable 3,000 3 165 300,000
104ST Series 91B-ST 3,000 3 165 300,000
105ST Series 91B-ST 3,000 3 165 300,000
105HIST Series 92-ST 3,000 8 440 800,000
867STR Series Not Replaceable 1,000 3 150 300,000
868STR Series Not Replaceable 1,000 3 150 300,000
869STR Series Not Replaceable 1,000 3 150 300,000

* Calculated at operating power to 75% efficiency.

** Also known as candela seconds. Refer to Technical Reference Appendix for calculation base.

Edwards Incandescent and Halogen Bulb Light Output

For halogen bulbs, the manufacturer's lumen rating is specified. (This measures effective light output in all directions). See Table 2 for bulb light output ratings.

Halogen and Incandescent Bulb Life

Light source life is also an area of some confusion as there are no current industry standards for measurement. At the same time ambient conditions (e.g. voltage & vibration) and duty cycles can significantly effect bulb life. Improper handling can also dramatically decrease both bulb and tube life.

When reporting bulb life Edwards is using manufacturer supplied data (which assumes a 100% constant duty cycle) and then interpolating the effects of the average flash rate (again assuming a constant duty cycle). See Table 2 for bulb Life ratings.

Table 2. Edwards Incandescent and Halogen Bulb Light Output and Life

Mfrs.
Lumen Calculated Projected
Cat. No. Bulb No. Bulb Rating Rating Lamp Life* Lamp Life**
48FIN-E1 Industry Trade 94 15W 189 700 1,520
48FIN-G1-20WH 50LMP-20WH 20W Halogen 226 20,000 25,000
Series or Industry Trade 1692
15W 110 1,000 6,350
48FIN-G5-20WH 50LMP-20WH 20W Halogen 226 20,000 25,000
Series or Industry Trade 1692
15W 110 1,000 6,350
48FIN-N5-25WH 50LMP-25WH 25W Halogen 175 20,000 25,000
Series or Industry Trade 25T8DC
48SIN-E1 Industry Trade 94 25W
15W
235
189
1,000
700
1,000
1,520
48SIN-G1-20WH 50LMP-20WH 20W Halogen 226 20,000 20,000
Series or Industry Trade 1692
15W 110 1,000 6,350
48SIN-G5-20WH 50LMP-20WH 20W Halogen 226 20,000 20,000
Series or Industry Trade 1692
15W 110 1,000 6,350
48SIN-N5-25WH 50LMP-25WH 25W Halogen 175 20,000 20,000
Series or Industry Trade 25T8DC
25W 235 1,000 1,000
49-N5-40WH Series 50LMP-40WH 40W Halogen 265 20,000 25,000
49-R5 Series P-041917-0039
or Industry Trade 25W 232 200 120
25T8/240V/DC/CL
50-G5-20WH Series 50LMP-20WH 20W Halogen 226 20,000 25,000
50-N5-40WH Series 50LMP-40WH 40W Halogen 265 20,000 25,000
50-R5 Series P-041917-0039
or Industry Trade 25W 232 200 120
25T8/240V/DC/CL
50SIN-N5-40WH 50LMP-40WH 40W Halogen 265 20,000 25,000
51-E1 Series Industry Trade 94 15W 189 700 1,520
51-G1 Series Industry Trade 1638 25W 402 500 3,180
51-G5-20W Series Industry Trade 1638 25W 402 500 3,180
51-N5-40W Series 50LMP-40W (6 ea) or 40W 266 1,500 3,920
P-041695-0118 (1ea)
51SIN-G1 Series Industry Trade 1638 25W 402 500 3,180
51SIN-N5-40W Series 50LMP-40W (6 ea) or 40W 266 1,500 3,920
P-041695-0118 (1ea)
52-N5 Series 50LMP-40WH 40W Halogen 265 20,000 25,000
52-G5 Series 50LMP-20WH 20W Halogen 226 20,000 25,000
52-R5 Series P-041917-0039
or Industry Trade 25W 232 200 120
25T8/240/DC/CL
52EX-N5-40W Series 50LMP-40W (6 ea) or 40W 266 1,500 3,920
P-041695-0118 (1ea)
52EXB-N5-40W 50LMP-40W (6 ea) or 40W 266 1,500 3,920
Series P-041695-0118 (1ea)
52EXC-N5-40W 50LMP-40W (6 ea) or 40W 266 1,500 3,920
Series
53-E1 Series
P-041695-0118 (1ea)
Industry Trade 1076
25W 402 200 430
53-G1 Series Industry Trade 1638 25W 402 500 3,180
53DR-GW Industry Trade 1638 25W 402 500 3,180
53DC-GW Industry Trade 1638 25W 402 500 3,180
53DEX-G1 Series Industry Trade 1638 25W 402 500 3,180
53DEXB-G1 Series Industry Trade 1638 25W 402 500 3,180
53DEXC-G1 Series Industry Trade 1638 25W 402 500 3,180
Mfrs.
Lumen Calculated Projected
Cat. No. Bulb No. Bulb Rating Rating Lamp Life* Lamp Life**
53EX-E1 Series Industry Trade 1076 25W 402 200 430
53EX-G1 Series Industry Trade 1638 25W 402 500 3,180
53EXB-E1 Series Industry Trade 1076 25W 402 200 430
53EXB-G1 Series Industry Trade 1638 25W 402 500 3,180
53EXC-E1 Series Industry Trade 1076 25W 402 200 430
53EXC-G1 Series Industry Trade 1638 25W 402 500 3,180
58-N5-100WH Series 100Q/CL/DC/ 120V 100W 1800 1,000 2,610
Halogen
101FIN-E1 Series Industry Trade 94 15W 189 700 1,520
101FINH-G1 Series 50LMP-9WH-D 9W Halogen 52 12,000 15,000
101FINH-N5 Series 50LMP-12WH-D 12W Halogen 70 20,000 25,000
101SIN-E1 Series Industry Trade 94 15W 189 700 1,520
101SINH-G1 Series 50LMP-9WH-D
or
9W Halogen 52 12,000 15,000
Industry Trade
101SINH-N5 Series 50LMP-12WH-D 12W Halogen 70 20,000 25,000
or Industry Trade
102LS-FIN-G1 Industry Trade 303 10W 66 10,000 10,000
102LS-FINH-G1 50LMP-9WH 9W Halogen 52 12,000 15,000
102LS-FIN-N5 50LMP-10W 10W 66 2,500 2,500
102LS-FINH-N5 50LMP-12WH 12W Halogen 70 20,000 25,000
102LS-SIN-G1 Industry Trade 303 10W 66 10,000 10,000
102LS-SINH-G1 50LMP-9WH 9W Halogen 52 12,000 15,000
102LS-SIN-N5 50LMP-10W 10W 66 2,500 2,500
102LS-SINH-N5 50LMP-12WH 12W Halogen 70 20,000 25,000
104FINH-G1 Series 50LMP-9WH-D 9W Halogen 52 12,000 15,000
or Industry Trade 1692 15W 110 1,000 6,350
104FINH-G5 Series 50LMP-9WH-D 9W Halogen 52 12,000 15,000
or Industry Trade 1692
15W 110 1,000 6,350
104FINH-N5 Series 50LMP-12WH-D 12W Halogen 70 20,000 25,000
or Industry Trade 15T7DC
15W 99 1,000 1,630
104SINH-G1 Series 50LMP-9WH-D 9W Halogen 52 12,000 15,000
or Industry Trade 1692
15W 110 1,000 6,350
104SINH-G5 Series 50LMP-9WH-D 9W Halogen 52 12,000 15,000
or Industry Trade 1692
15W 110 1,000 6,350
104SINH-N5 Series 50LMP-12WH-D 12W Halogen 70 20,000 25,000
or Industry Trade 15T7DC
15W 99 1,000 1,630
105FINH-G1 Series 50LMP-20WH 20W Halogen 226 20,000 25,000
105FINH-G5 Series 50LMP-20WH 20W Halogen 226 20,000 25,000
105FINH-N5 Series 50LMP-25WH 25W Halogen 175 20,000 20,000
105SINH-G1 Series 50LMP-20WH 20W Halogen 226 20,000 25,000
105SINH-G5 Series 50-LMP-20WH 20W Halogen 226 20,000 25,000
105SINH-N5 Series 50LMP-25WH 25W Halogen 175 20,000 20,000

* Calculated by the manufacturer at continuous operation at operating voltage.

Edwards LED Light Output

For LEDs, the manufacturer's lumen rating per LED is used as the basis for calculations. However it should be noted that with LEDs light output ratings are relatively meaningless as LED viewing angle and lens optics have a more significant effect on viewer perceptibility.

** Projected at 65FPM and 50% duty cycle.

Table 3. Edwards LED Light Output and Life

Cat. No. LED Color LED Life (hrs) Lumen Rating
101FLED-G1 Red 100,000 28
101FLED-G1 Amber 100,000 38
101FLED-G1 Blue 100,000 35
101FLED-G1 Green 100,000 102
101FLED-N5 Red 100,000 28
101FLED-N5 Amber 100,000 38
101FLED-N5 Blue 100,000 35
101FLED-N5 Green 100,000 102
101SLED-G1 Red 100,000 28
101SLED-G1 Amber 100,000 38
101SLED-G1 Blue 100,000 35
101SLED-G1 Green 100,000 102
101SLED-N5 Red 100,000 28
101SLED-N5 Amber 100,000 38
101SLED-N5 Blue 100,000 35
101SLED-N5 Green 100,000 102
102FLED-G1 Red 100,000 135
102FLED-G1 Amber 100,000 346
102FLED-G1 Blue 100,000 135
102FLED-G1 Green 100,000 135
102FLED-N5 Red 100,000 135
102FLED-N5 Amber 100,000 346
102FLED-N5 Blue 100,000 135
102FLED-N5 Green 100,000 135
102SLED-G1 Red 100,000 135
102SLED-G1 Amber 100,000 346
102SLED-G1 Blue 100,000 135
102SLED-G1 Green 100,000 135
102SLED-N5 Red 100,000 135
102SLED-N5 Amber 100,000 346
102SLED-N5 Blue 100,000 135
102SLED-N5 Green 100,000 135
48FLED-G1 Red 100,000 28
48FLED-G1 Amber 100,000 38
48FLED-G1 Blue 100,000 35
48FLED-G1 Green 100,000 102
48FLED-N5 Red 100,000 28
48FLED-N5 Amber 100,000 38
48FLED-N5 Blue 100,000 35
48FLED-N5 Green 100,000 102
48SLED-G1 Red 100,000 28
48SLED-G1 Amber 100,000 38
48SLED-G1 Blue 100,000 35
48SLED-G1 Green 100,000 102
48SLED-N5 Red 100,000 28
48SLED-N5 Amber 100,000 38
48SLED-N5 Blue 100,000 35
48SLED-N5 Green 100,000 102
103-RBA-G1 Red 100,000 120
Blue 100,000 90
Amber 100,000 307
103-RGA-G1 Red 100,000 120
Green 100,000 90
Amber 100,000 307
Cat. No. LED Color LED Life (hrs) Lumen Rating
103-RBA-N5 Red 100,000 120
Blue 100,000 90
Amber 100,000 307
103-RGA-N5 Red 100,000 120
Green 100,000 90
Amber 100,000 307
103I-RBA-G1 Red 100,000 120
Blue 100,000 90
Amber 100,000 307
103I-RGA-G1 Red 100,000 120
Green 100,000 90
Amber 100,000 307
103I-RBA-N5 Red 100,000 120
Blue 100,000 90
Amber 100,000 307
103I-RGA-N5 Red 100,000 120
Green 100,000 90
Amber 100,000 307
104FLED-G1 Red 100,000 28
104FLED-G1 Amber 100,000 38
104FLED-G1 Blue 100,000 35
104FLED-G1 Green 100,000 31
104FLED-N5 Red 100,000 28
104FLED-N5 Amber 100,000 38
104FLED-N5 Blue 100,000 35
104FLED-N5 Green 100,000 31
104SLED-G1 Red 100,000 28
104SLED-G1 Amber 100,000 38
104SLED-G1 Blue 100,000 35
104SLED-G1 Green 100,000 31
104SLED-N5 Red 100,000 28
104SLED-N5 Amber 100,000 38
104SLED-N5 Blue 100,000 35
104SLED-N5 Green 100,000 31
105FLED-G1 Red 100,000 28
105FLED-G1 Amber 100,000 38
105FLED-G1 Blue 100,000 35
105FLED-G1 Green 100,000 102
105FLED-N5 Red 100,000 28
105FLED-N5 Amber 100,000 38
105FLED-N5 Blue 100,000 35
105FLED-N5 Green 100,000 102
105SLED-G1 Red 100,000 28
105SLED-G1 Amber 100,000 38
105SLED-G1 Blue 100,000 35
105SLED-G1 Green 100,000 102
105SLED-N5 Red 100,000 28
105SLED-N5 Amber 100,000 38
105SLED-N5 Blue 100,000 35
105SLED-N5 Green 100,000 102

Technical Reference Information Light Output Descriptions

When comparing two different warning lights, the first question usually asked is how bright are these lights and how do they compare to one another? This can be a complicated question when one is comparing very different light sources such as rotating incandescent lights and xenon strobe lights. Three different commonly used specified "intensity" ratings are discussed below.

  • 1. PEAK CANDELA or PEAK CANDLEPOWER This quantifies the maximum light intensity generated by a flashing light during its light pulse. It indicates nothing about how bright the light appears to the human eye. Peak candela alone cannot be used to directly compare two warning lights. In addition there is no set multiplication factor for converting peak candela, a unit of luminous intensity, to either candela seconds or effective candela, both units of luminous energy.
  • 2. CANDELA SECONDS or CANDLEPOWER SECONDS This quantifies the actual light energy contained in a pulse of light. Candela seconds is used by SAE (Society of Automotive Engineers) and by most State Highway Patrol Divisions to specify the minimum requirements of light output from a flashing light because flash energy has been shown to be a relatively accurate and fair way of comparing radically different types of lights such as incandescent rotators and xenon strobe lights.
  • 3. EFFECTIVE CANDELA or EFFECTIVE CANDLEPOWER Effective candela is based on candela seconds and attempts to equate the brightness of a flashing light source to the brightness of a steady burning source. If a flashing light has an effective candela rating of 100 then it will be visible at the same distance as a 100 candela steady burn source. The National Bureau of Standards, the FAA, and the Illuminating Engineering Society use effective candela in specifying intensities of flashing light sources because this rating is the most meaningful when it becomes necessary to predict the visible range of flashing lights verses steady burn light sources.

Since one unit of "this" doesn't really equal two units of "that", the lighting manufacturing industry in general assimilates for easy laymen terms the following:

50 Candela assimilates to 100,000 Peak Candlepower which assimilates to 1 Joule

Just remember, a Joule is a measurement of electric energy, while Candlepower is a measurement of apparent brightness. Therefore, these comparisons are only approximate.

As shown in the diagram on the right, a strobe will have a much higher peak candela rating than a halogen rotator. However, the overall effective intensity is determined by the area under the curve. In comparing the two lights, the halogen rotator would have a higher perceived brightness of the two lights.

Strobe vs. Halogen Rotator Intensities

Technical Reference Information Output Flash Brightness

Approximate Effective Candela Rating per Joule:

Lens Color Strobe Output Halogen Output
Clear 45-55 Candela/Joule 45-55 Candela/Joule
Amber 30-40 Candela/Joule 32-43 Candela/Joule
Blue 17-23 Candela/Joule 7-10 Candela/Joule
Green 15-20 Candela/Joule 7-15 Candela/Joule
Red 7-10 Candela/Joule 10-15 Candela/Joule

Please note that the actual light output of a typical strobe warning light will depend upon a number of factors. These factors can vary the light output by a factor of 10 or more for a given number of Joules per flash. Joules is a measurement of electric energy, while Candela is a measurement of apparent brightness. Some of the factors involved are:

  • -Color of lens
  • -Size and efficiency of lens
  • -Physical shape of strobe lamp and arrangement within the lens (optical coupling)
  • -Efficiency of the strobe lamp itself

Determining Effective Candela:

Candela/Joule Rating
10 15 20 25 30 35 40 45 50
Flash 3 Joules 30 45 60 75 90 105 120 135 150
Power 10 Joules 100 150 200 250 300 350 400 450 500
15 Joules 150 225 300 375 450 525 600 675 750

Example: For a 10 Joule light in an Amber lens:

10 Joules x 40 Candela/Joule = 400 Effective Candela since 50 Candela assimilates to 100,000 Peak Candlepower = 400 Effective Candela x 100,000/50 = 800,000 Peak Candela