Edwards Signaling Data Sheet K85001-0616 – EC5000R Reflective Beam Detector

Open the original PDF document

View PDF

Technology that saves lives

Reflective Beam Smoke Detector

EC5000R

Overview

The EC5000R comprises a transmitter and receiver in a single enclosure. The transmitter emits an invisible infrared light beam that is reflected via a reflector mounted directly opposite and within a clear line of sight. The reflected infrared light is detected by the receiver and analyzed. Smoke in the beam path will reduce the received infrared light proportionally to the density of the smoke. The detector analyzes this attenuation and initiates an alarm condition when a predetermined level of obscuration is reached.

The EC5000R System features advanced innovations such as auto-alignment, which indicates the optimal location of the reflector by means of an integrated laser. Once installed, the system automatically steers and maintains the beam to the optimum position for reliable performance.

Standard Features

  • Range of 26.25 to 330 ft. (8 m to 100 m)
  • Ground level controller with LCD display for easy system maintenance and testing
  • Up to two detector heads reporting to one controller
  • Laser-assisted prism mounting speeds installation
  • Automatic beam alignment increases reliability
  • Contamination compensation reduces nuisance alarms
  • Building shift compensation maintains system integrity
  • Separate alarm and trouble contacts for easy configuration
  • Built-in electronic UL/ULC obscuration accepted fire test
  • Password protected settings for added security
  • Programmable fire thresholds for application flexibility

Application

Reflective beam smoke detectors are ideal for large open areas such as warehouses, hotel atrium, industrial plants and school gymnasiums.

An infrared signal is projected out of the transmitter optics to the reflector placed at the opposite end of the detection zone. The signal is reflected back to the receiver where it is analyzed for fire and trouble. The maximum lateral distance either side of the beam is found to be typically 30 feet (9.1 m) for satisfactory detection under flat ceilings, providing a total area coverage of 19,800 square feet (60 feet x 330 feet), or 1844 square metres (18.3 x 100.6 m).

Smoke stratification may be overcome by mounting multiple beam detectors at different heights, one of which will project an infrared beam below the heat layer and into the smoke layer.

Detection time will be longer in a building with a peaked roof if a fire occurs at the fringes of the protected area. If in doubt conduct appropriate smoke tests.

The ideal location and spacing of the detector is critical in a properly installed and operating fire alarm system. It is recommended that the detectors be located and spaced in accordance with NFPA 72.

The recommended installation height is approximately 19 to 24 inches (483 to 610 mm) below the ceiling. However, in all installations the National Fire Standards for that country/state must be consulted.

Because of the reflecting properties of the beam, all objects must be kept a minimum of 19 inches (483 mm) away from the centre of the beam path down the entire beam length. If highly reflective surfaces are close to the beam, then greater clearances should be applied.

Reflector Positioning

Mount the reflector(s) on a secure surface directly opposite the detector. Ensure that there is a clear line of sight between the detector and the reflector(s), and that no moving objects such as doors or mechanical equipment interfere with the beam path. All objects should be kept away from the center of the detector beam down the entire length of the beam path. Reflectors should not be mounted on glass or reflective surfaces.

EC5000R detectors come standard with a single reflector, which should be mounted between 27 and 160 feet (8 and 50 m) from the detector.

Single reflector

For detector/reflector distances of 160 to 330 ft (8 to 100 m), order a Long-Range Reflector Kit. This provides three additional reflectors for grouping as shown at right.

See the Ordering Table for available mounting brackets and options.

Group of four reflectors

Detector Spacing

Detector positioning shown here is recommended for protected areas with flat ceilings. Spacing may vary for areas with high or sloped ceilings. In such cases, verify operation with smoke tests.

In some cases potential smoke layering may be overcome by installing multiple beam detectors at different heights.

Typical Wiring

The field wiring interface is accessed through the back plate of the detector head. The 8-pin connector is the interface to the field and is numbered left to right. This diagram is an example for a single reflective beam unit installed as the only device on a zone. The correct operation for Fire and Trouble should always be verified. Relays are shown in quiescent (standby) condition. Alarm and End of Line resistor values are determined by the fire alarm control panel and market standard practices.

Zone Wiring

Engineering Specification

The projected beam type smoke detector shall be listed to UL 268 listed and shall consist of up to two integrated transmitters, receiver detector heads and single low level remote control unit. The detector shall operate between a range of 26.25 ft. to 330 ft. (8m to 100m). The temperature range of the system shall be -4°F to 131°F (-20°C to 55°C). The beam detector heads shall include an integral built-in laser pointer to assist prism mounting. The beam detector shall feature automatic gain control which will compensate for gradual signal deterioration from dirt accumulation on the lenses. The beams detector heads shall include AutoOptimise self-correcting motorized head feature to ensure unit is always receiving maximum signal available, and shall automatically compensate for building shift. The unit shall include a low level remote display and control unit with LCD read-out for set-up, reporting and testing of up to two separate detector heads. The system shall be capable of programming alarm thresholds of 10% to 60% in 1% increments. The system shall be capable of programming delay to fault and delay to alarm from 2 seconds to 30 seconds in 1 second increments. Test and acceptance of the system shall be carried out by using the UL approved internal electronic obscuration fire test. The projected beam type smoke detector shall be a 4-wire 24 VDC device to be used with a Nationally Recognized Testing Laboratory's Listed separately supplied 4-wire control panel. The Reflective beam type smoke detector shall be a Fire Fighting Enterprises Fireray 5000.

Dimensions

Technical Specifications

Technical Specifications
Electrical
Primary Input 14 to 36 VDC
Standby Current Low Current Mode: 5 mA to 8.5 mA @ 24 VDC
depending on number of detector heads used.
High Current Mode: 37 mA @24 VDC
Alarm Current 5 mA to 8.5 mA @ 24 VDC
depending on number of detector heads used
Relay Contacts 1 A at 30 VDC Resistive
Reset Time 5 Seconds maximum
Start Up Time 45 Seconds
Optical Wavelength 850 nm
Alarm Threshold 10% - 60% (35% Default)
Temperature -4 °F to 131 °F (-20 °C to 55 °C).
Rating UL Listed Installations:
32 °F to 100 °F (0 °C to 37.8 °C).
Relative Humidity 0% to 93% RH non-condensing
Range 26.25 ft. to 330 ft. (8 m to 100 m)
Cabling Between detectors and controllers 24 to 14 AWG.
One pair, shielded.
Physical
Housing Flame Retardant ABS
IP Rating IP54
Physical
Housing Flame Retardant ABS
IP Rating IP54
Finish Light Grey/Black
Conduit Controller: 7— 1/2"/M-20
Knockouts Detector Head—1 M-20
Weight: Head & Controller: 3.24 lbs (1.47 kg)
Dimensions Head: 5.28" H x 5.16" L x 5.28" W
(135mm H x 131mm L x 134mm W
Controller: 3.43" H x 9.06" L x 7.95" W
(87mm H x 230mm L x 202mm W)
Prism: 0.37" H x 4.13" L x 3.94" W
(9.5mm H x 105mm L x 100mm W)
Agency Listings
UL, ULC S529 (File no. S3417) CSFM (File no. 7260-1508-104)
MEA (File no. 22-08-E) FM Approved

Technology that saves lives

Contact us...

Email: kidde.fire@fs.utc.com Web: Kidde.com/EngineeredSystems

Kidde is a UTC brand. 1016 Corporate Park Drive Mebane, NC 27302

© 2016 United Technologies Corporation. All rights reserved.

Ordering Information

EC5000R Reflective auto align beam smoke detector system. Includes one detector head,
one controller, one prism.
Accessories
EC5000X Additional Detector head and one prism, for use on EC5000R
5000-004 Long Range Prism Kit - 3 additional prisms
for installations between 160ft and 330ft (50m-100m)
5000-005 Universal Alignment bracket
5000-201 Universal 130 degree alignment bracket
5000-006 Wall bracket mounts, 1 or 4 prisms
5000-007 4 prism alignment adapter plate
5000-008 1 prism alignment adapter plate
5000-009 Controller back box
5000-010 Semi flush trim plate for 5000-009
5000-011 Detector surface mount uni-box
5000-012 Detector 2 gang mounting plate
5000-014 Ceiling Pendant mount bracket