Edwards Signaling 2447T Integrity Temporal Horn Installation Sheet

Open the original PDF document

View PDF

Integrity Temporal Horn Installation Sheet

Description

The Integrity Temporal Horn is a fire alarm notification appliance designed for indoor or outdoor walls and ceilings. See Table 1 for temporal horn model numbers and Table 2 for accessory model numbers.

Table 1: Models

Description Numbers
Temporal horn, red 757-1A-T
XLS757-1A-T
INT-T
2447TH-R
Temporal horn, white 757-1A-TW
XLS757-1A-TW
INT-TW
2447TH-W

Table 2: Accessories

Description Numbers
Surface box, red, indoor 757A-SB
XLS757A-SB
INT-SB
2459-SMB-R
Surface box, white, indoor 757A-SBW
XLS757A-SBW
INT-SBW
2459-SMB-W
Weatherproof box, red,
outdoor
757A-WB
XLS757A-WB
INT-WB
2459-WPB-R
Weatherproof box, white,
outdoor
757A-WBW
XLS757A-WBW
INT-WBW
2459-WPB-W
Bi-directional mounting
frame, red, indoor
757A-BDF
XLS757A-BDF
INT-BDF
Bi-directional mounting
frame, white, indoor
757A-BDFW
XLS757A-BDFW
INT-BDFW

Installation

WARNING: Electrocution hazard. To avoid personal injury or death from electrocution, remove all sources of power and allow stored energy to discharge before installing or removing equipment.

Note: Electrical supervision requires the wire run to be broken at each terminal. Do not loop the signaling circuit field wires around the terminals.

Install this product in accordance with applicable requirements in the latest editions of NFPA 72 National Fire Alarm and Signaling Code, CSA C22.1 the Canadian Electrical Code, Part 1, Section 32, CAN/ULC-S524 Installation of Fire Alarm Systems, and in accordance with the local authority having jurisdiction.

To install the temporal horn:

  • 1. Select and install a suitable electrical box. See "Mounting the electrical box" on page 2 for details.
    • Note: Outdoor installations require a weatherproof backbox.
  • 2. Set the tone and pattern. See "Selecting the volume and pattern" on page 2 for details.
  • 3. Bring the signal circuit field wiring into the electrical box.
  • 4. Position the mounting plate on the electrical box with the hook flange up and facing outward as shown in Figure 2. Fasten the plate using the screws provided.
  • 5. Connect the signal circuit field wiring. For the unit to function properly, observe polarity. See Figure 1.
    • For additional wiring details, see the installation instructions for the signaling modules or circuits used in the fire alarm control panel.
  • 6. After completing the connections, attach the unit to the mounting plate, as noted below.
    • a. The grille has tabs (at the top of the inner face) that engage with the hook flange on the mounting plate. Angle the bottom of the grille out slightly, and then slide the unit into place so that the tabs engage the flange.
    • b. Seat the grille by pressing the bottom in.
    • c. Fasten the bottom of the grille to the mounting plate by tightening the captive locking screw.
  • 7. Apply power and activate the unit to verify that it is operating properly.

Figure 1: Typical wiring diagram

Polarity is shown in the active state.

  • (1) From UL/ULC Listed fire alarm control panel signal circuit.
  • (2) To next device or end of line resistor for Class B. Return to control panel for Class A connection.

  • (1) Gasket with adhesive backing
  • (2) Weatherproof box
  • (3) Standard box
  • (4) Knockouts for 1/2 in. (13 mm) or 3/4 in. (19 mm) conduit top, bottom, back
  • Mounting the electrical box

Figure 2 shows mounting details for:

  • Standard box. When using a 4 in. square box, use an extension ring for additional wiring space, if needed. If using a double-gang electrical box that is 2-1/2 in. (64 mm) deep, locate the conduit only at the rear of the box.
  • Weatherproof box. Peel off the adhesive backing from the gasket and adhere to the box.
  • Surface mount box.

Selecting the volume and pattern

The horn has a jumper for selecting a high or low volume output level. The default is high volume. To set the output to low volume, remove the output jumper from the circuit board on the rear of the unit. See Figure 3.

The horn has a jumper for selecting either a temporal or steady tone. The default is temporal tone. To set the output to steady tone, remove the tone jumper from the circuit board on the rear of the unit. See Figure 3.

Tip: Save the jumper by sliding it onto a single pin.

  • (5) Surface mount box
    • (6) Mounting plate (supplied with horn)
    • (7) #8-32 screw
    • (8) Captive locking screw
    • (9) Hook flange

Figure 3: Jumper setup and terminal block

Item In Out
(1) High output Low output
(2) Temporal tone Continuous tone

Maintenance

Note: Do not change the factory-applied finishes.

This unit is not serviceable or repairable. Should the unit fail to operate, contact the supplier for replacement.

Perform a visual inspection and an operational test twice a year or as directed by the local authority having jurisdiction.

Specifications

Operating voltage 16 to 33 VDC; 16 to 33 VFWR
Operating current
16 to 33 VDC 85 mA
16 to 33 VFWR 105 mA
Sound output See Table 3 and Table 4
Synchronization Pulses at temporal rate within 200 ms on
common circuit for 30 minutes
Horn temporal pattern 0.5 s on, 0.5 s off, 0.5 s on, 0.5 s off, 0.5 s
on, 1.5 s off, repeat cycle
Wire size 12 to 18 AWG (0.75 to 2.50 mm²)
Compatible electrical
boxes
2-1/2 in.(64 mm) deep double-gang;
Standard 4 in. square box 2-1/8 in. (54 mm)
deep; surface or weatherproof mounting box
per Table 1
Operating temperature
Indoor 32 to 120°F (0 to 49°C)
UL outdoor −31 to 150°F (−35 to 66°C)
ULC outdoor −40 to 150°F (−40 to 66°C)
Relative humidity
Indoor 93% noncondensing
Outdoor 98% noncondensing

Table 3: Reverberant room sound output (dBA) [1]

Method Temporal Continuous
Low High Low High
UL464 at 16 VDC 73 80 77 83
ULI at 24 VDC 77 83 82 86
ULI at 33 VDC 78 85 82 88

[1] Sound level output at 10 ft. (3.05 m)

Table 4: ULC anechoic room sound output (dBA) [1]

Method Temporal Continuous
Low High Low High
16 to 33 VDC 93 98 86 91
16 to 33 VFWR 96 100 90 93

[1] Average peak sound level output at 10 ft. (3.05 m)

Meets or exceeds CAN/ULC-S525-07, 85 dBA minimum anechoic at 3 meters, all settings

Table 5: ULC directional characteristic

Angle dBA
90° 0 (ref)
57° and 123° −3
37° and 143° −6

Note: Horizontal and vertical axes provide the same pattern.

Regulatory information

Manufacturer Edwards, A Division of UTC Fire & Security
Americas Corporation, Inc.
8985 Town Center Parkway, Bradenton, FL
34202, USA
Year of
manufacture
The first two digits of the date code (located on
the product identification label) are the year of
manufacture.
UL/ULC rating Regulated 24 DC and Regulated 24 FWR [1]
Environmental
class
Indoor or outdoor
North American
standards
Meets: UL 464 and CAN/ULC-S525-07
Follow: NFPA 72 and CAN/ULC-S524
2002/96/EC (WEEE directive): Products marked
with this symbol cannot be disposed of as
unsorted municipal waste in the European Union.
For proper recycling, return this product to your
local supplier upon the purchase of equivalent
new equipment, or dispose of it at designated
collection points. For more information see:
www.recyclethis.info.

[1] This device was tested to the regulated 24 DC/FWR operating voltage limits of 16 V and 33 V.

Contact information

For contact information, see www.utcfireandsecurity.com.