DynaLock 5600 Series Installation Instructions

Open the original PDF document

View PDF

705 Emmett Street Bristol, CT 06011-2728 Phone:(860) 582-4761 • Fax:(860) 585-0338

MODEL #5600 POWER SUPPLY

INSTALLATION INSTRUCTIONS

5600 Manual 03/03

Phone:(860) 582-4761 Fax:(860) 585-0338

MODEL #5600 POWER SUPPLY

INSTALLATION INSTRUCTIONS

FAC Option (Fire Alarm Control)

Kills all voltage outputs when interfaced with emergency system dry contact.

12V FAC module #500253 24V FAC module #500254

Typical Application

Normally-Closed Dry Contact from Fire Alarm Control Panel (By others). Cut Main Board Jumper when field installed. Refer to Page #1 (FAC Jumper).

Connector for

FACMR Option (FAC Manaul Reset)

Opening normally closed contact removes all output power until the normally open reset button is momentarily pressed.

DB-5 & DB-10 Option (Distribution Board)

Two size distribution boards (5 or 10 position) are available to provide individually fused output terminals for each lock zone.

*Resettable Fuse Supply Main Board

*Resetting is done by first correcting the overload then disconnecting the load or turning off the line voltage for two minutes.

CM Option (Control Module)

(Factory Setting)

Accepts access/egress control dry contact input. Provides SPDT relay output.

Without Control Module Option With Control Module

Access Control Input, Dry Contacts Only. A

DC Input from Power

POWER SUPPLY 705 Emmett Street Bristol, CT 06011-2728 Phone: (860) 582-4761 • Fax: (860) 585-0338

INSTALLATION INSTRUCTIONS

MODEL #5600

CMTD Option (Control Module with Time Delay)

Same as CM Option with Relock Time Delay

  • (A) Access Control Input, Dry Contacts Only.
  • (B) SPDT Dry Contacts Rated 2A @ 24V.

Note: Separate ILB user manual shows typical wiring diagrams.

ATS Option

(Anti-Tamper Switch)

Contact held open with Enclosure cover closed.

Contact closed with Enclosure cover open.

NOTE: ATS switch contacts rated .25A @ 24V.

Installation Information

LOCK CAPACITY CHART

Single Full
Size
Double Full
Size
Single Double Single Delay
Egress
Deadbolt
12VDC 18 9 18 9 11 10
24VDC 18 9 18 9 8 9

CURRENT DRAW UP TO 1/2 AMP

Voltage 20 AWG 18 AWG 16 AWG 14 AWG 12 AWG 10 AWG
12VDC 50Ft. 100Ft. 150Ft. 250Ft. 400Ft. 625Ft.
24VDC 150Ft. 225Ft. 350Ft. 550Ft. 900Ft. 1375Ft.

* This chart indicatess minimum recommended wire size, but local codes prevail

705 Emmett Street Bristol, CT 06011-2728 Phone:(860) 582-4761 Fax:(860) 585-0338

MODEL #5600 POWER SUPPLY

INSTALLATION INSTRUCTIONS

TROUBLESHOOTING

  • 1 Check input line power.
  • 2 Check line fuse.
  • Check For 12 or 24 VDC from 3
  • Switcher. 4
  • Check F2 & F3 output fuses. Check that FAC Module is properly 5a
  • seated. (If applicable) Terminals 1 & 2 must be jumpered if 5b
  • unit has FAC Module. 5c

Note: Start at ' No Output Power @ A

A B

  • Check jumper settings on CM/CMTD module(If applicable). 6
  • Check jumper setting on DB-5/DB-10 card. 7
  • Check for proper access switch contact status. 8
  • Check load & external wiring for short condition. 9
  • Reset Power Supply (With no load) by disconnecting input power at for 2 minutes. 1 10

5600 Manual 03/03 Page #4

No Output Power @ No Output @